Conecte dispositivos Modbdus RTU / ASCII à rede PROFIBUS DP utilizando o Gateway PROFIBUS para Modbus RTU / ASCII GW-7552

  • Protocol & Hierarchy : DP-V0 Slave
  • Transmission Rate Setting : detected automatically
  • Address Setting : 0~126 set by DIP switch
  • Supports Modbus Mode : Master/Slave
  • Supports Modbus Format : RTU/ASCII

Gateway PROFIBUS Modbus RTU / ASCII GW-7552-B

O Gateway PROFIBUS Modbus RTU / ASCII GW-7552-B foi projetado para conectar rapidamente dispositivos Modbus à redes e controladores com protocolo PROFIBUS DP.

Permite que o mestre PROFIBUS acesse os dispositivos Modbus, esses dispositivos Modbus podem ser um PLC, um sensor, módulos da série ICPDAS M-7000 e assim por diante.

Além disso, também fornecemos o software utilitário para os usuários configurarem o GW-7552. Ao utilizar este módulo, os usuários podem colocar seus dispositivos Modbus na rede PROFIBUS com muita facilidade.

PROFIBUS para Modbus RT ASCII

 

Destaques Gateway PROFIBUS Modbus RTU / ASCII GW-7552-B

  • Protocol & Hierarchy : DP-V0 Slave
  • Supports PROFIBUS Transmission Rate (Kbps) : 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
  • Transmission Rate Setting : detected automatically
  • Max Input Data Length : 132 Bytes
  • Max Output Data Length : 131 Bytes
  • Address Setting : 0~126 set by DIP switch
  • Supports Modbus Mode : Master/Slave
  • Supports Modbus Format : RTU/ASCII
  • Hybrid COM 1 : RS-232/422/485 with “Self Tuner” inside
  • Supports COM 1 Baudrate (Kbps) : 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2
  • Supports COM 1 Data Format : 7/8 data bits, No/Odd/Even parity, 1/2 stop bit
  • Indicators : PWR, ERR, and RUN LEDs
  • Network Isolation Protection : High Speed iCoupler
  • DC Isolation Protection : 3000VDC on PROFIBUS side

 

CPU Module
CPU 80186, 80 MHz or compatible
EEPROM 16 KB
Flash 512 KB
SRAM 512 KB
Watchdog Timer Watchdog IC
CPU built-in
LED Indicators
Status PWR LED, RUN LED, ERR LED
COM Ports
Ports RS-232/RS-422/RS-485(can’t be used simultaneously)
3-pin screwed terminal block (RxD, TxD, GND)
4-pin screwed terminal block (RxD+, RxD-, TxD+, TxD-)
2-pin screwed terminal block (DATA+, DATA-)
Baud Rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Parity None, Even, Odd
Data Bit 7, 8
Stop Bit 1, 2
PROFIBUS
Controller Siemens SPC3
Transceiver ADI ADM2486
Baud Rate 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol DP-V0
Power
Consumption 2.5 W
Mechanical
Dimensions (mm) 72 x 33 x 119 (W x L x H)
Installation DIN-Rail
Environmental
Operating Temperature -25 ~ +75℃
Storage Temperature -30 ~ +85 ℃
Humidity 5 ~ 95% RH, Non-condensing